Product Name: 52 kV RIP Bushings for Transformer
Company: Shandong ChinSun Electrical Equipment Co., Ltd.
Rated Voltage: 52 kV
Rated Current: 1600 A
One-Minute Power Frequency Withstand Voltage (Dry): 155 kV
Partial Discharge Level at Rated Maximum Voltage (Um): ≤10 pC
Tangent of Loss Angle (Tanδ) of Bushings: ≤0.5%
Lightning Impulse Withstand Voltage: 325 kV
Conductor Material: Copper
Creepage Distance (External): ≥ [value missing]
Installation Angle Range: 0-60°
Ambient Temperature Range: -40ºC to +50ºC
Pollution Class: IV
Cantilever Test Load: 4000 N
Maximum Mounting Height: ≤1500 m
Internal Insulation: Resin Impregnated Paper (RIP)
External Insulation: porcelain
Compliance with Standard: IEC 60137
Description: 52 kV porcelain type of bushings for power transformers
52 kV Transformer Bushings
Upgrade your power transformers with high-voltage bushings from Shandong ChinSun Electrical Equipment Co., Ltd. These bushings feature silicone rubber sheds and are made of composite polymer material, ensuring optimal transformer insulation. Enhance the efficiency and reliability of your transformers with these top-quality bushings.
Key technical parameters-IEC 60137-2017 | ||||||||||||||
Standard | IEC 60137-2017 | |||||||||||||
Highest voltage for equipment Um | kV | 24 | 36 | 52 | 72.5 | 100 | 123 | 145 | 170 | 245 | 300 | 362 | 420 | 550 |
Rated frequency | Hz | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 |
Dry power frequency withstand voltage 1minute |
kV | 55 | 77 | 105 | 155 | 205 | 255 | 305 | 355 | 505 | 505 | 560 | 750 | 870 |
Lightning impulse(BIL) | kV | 125 | 170 | 250 | 325 | 450 | 550 | 650 | 750 | 1050 | 1050 | 1175 | 1550 | 1800 |
Switching impulse(SIL) | kV | - | - | - | - | - | - | - | - | 850 | 850 | 950 | 1175 | 1300 |
Maximum Rated Current (Draw-lead/removeable rod) |
A | 1250/ 2000 | 1250/ 2000 | 1250/ 2000 | 1250/ 2000 | 1250/ 2000 | 1250/ 2000 | 1250/ 2000 | 1250/ 2000 | 1250/ 2000 | 1250/ 2000 | 1250/ 2000 | 1250/ 2000 | 1250/ 2000 |
Maximum Rated Current (Solid conductor) |
A | 4000 | 4000 | 4000 | 3150 | 3150 | 3150 | 3150 | 3150 | 3150 | 3150 | 3150 | 3150 | 3150 |
Temperature range | ºC | Down to -60°C up to +55°C available on request | ||||||||||||
Key technical parameters-IEEE C57.19.01-2017 | ||||||||||||||
Standard | IEEE C57.19.01-2017 | |||||||||||||
Highest voltage for equipment Um | kV | 25 | 34.5 | 46 | 69 | 115 | 138 | 161 | 230 | 345 | 500 | |||
Rated frequency | Hz | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | |||
Dry power frequency withstand voltage 1minute |
kV | 60 | 80 | 105 | 160 | 260 | 310 | 365 | 425 | 520 | 750 | |||
Lightning impulse(BIL) | kV | 150 | 200 | 250 | 350 | 550 | 650 | 750 | 900 | 1175 | 1675 | |||
Switching impulse(SIL) | kV | - | - | - | - | - | - | - | - | 825 | 1175 | |||
Maximum Rated Current (Draw-lead/removeable rod) |
A | 800/ 2000 | 800/ 2000 | 800/ 2000 | 800/ 2000 | 800/ 2000 | 800/ 2000 | 800/ 2000 | 800/ 2000 | 800/ 2000 | 800/ 2000 | |||
Maximum Rated Current (Solid conductor) |
A | 5000 | 5000 | 4000 | 4000 | 3000 | 4000 | 3000 | 5000 | 3000 | 3000 | |||
Temperature range | ºC | Down to -60°C up to +55°C available on request |
Rip Bushings, Bushings for Oil Circuit Breaker, 220kV Bush, Oil Circuit Breaker Bushings, Rip Bushings for Breaker, 220kV Circuit Breaker Bush, Insulator Bushings for Switchgear, Polymer Bushings for Power System, Resin Bushings for High Voltage, Porcelain Bushings for Transformer, Bushings for GIS Equipment, Outdoor Circuit Breaker Bushings, Cable Termination Bushings, Circuit Breaker Bushings, Safety Bushings, Oil Breaker Bushings, 220kV Bushings, Porcelain Bushings, GIS Equipment Bushings, Outdoor Bushings
Shandong ChinSun Electrical Equipment Co., Ltd. is a leading provider of high-quality electrical equipment.
Our 52kV - 550kV Transformer Bushings are designed to provide reliable insulation for high voltage applications. These bushings are suitable for various uses, including oil circuit breakers, switchgear, power systems, and transformers. Made from durable materials such as polymer, resin, and porcelain, our bushings ensure safe and efficient operation of your equipment. With a focus on quality and performance, our bushings are a trusted choice for GIS equipment, outdoor installations, and cable terminations. Trust Shandong ChinSun Electrical Equipment Co., Ltd. for all your insulator needs.