Customization: | Available |
---|---|
Application: | High-voltage |
Material: | Porcelain |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Rated voltage (Ur): 69 kV
Maximum operating voltage (Um): 72.5 kV
Rated frequency: 50/60 Hz
Rated current: 630 A
1-minute power-frequency withstand voltage (dry): 140 kV
Partial discharge level at Um: ≤5 pC
Tanδ of bushings: ≤0.4%
Lightning impulse withstand voltage (dry): 325 kV
Rated thermal short-time current, 1 sec (Ith): 15.75 kA
Rated dynamic current (Id): 39.375 kA
Material of conductor: Aluminum (AL)
Test tap voltage withstand level: 2 kVrms
Creepage distance (outdoor): not less than 2240 mm
Creepage distance (indoor): not less than 1990 mm
Installation angle: 0-90°
Altitude above mean sea level: ≤1000 m
Test cantilever load: 2000N
Ambient temperature range: -30°C to +55°C
Internal insulation: Resin Impregnated Paper (RIP)
External insulation/Colour: Porcelain covered with Polymeric Room Temperature Vulcanizing (PRTV) silicone rubber / Brown
Compliance with standard: IEC 60137
Company name: Shandong Chinsun Electrical Equipment Co., Ltd.
Key technical parameters-IEC 60137-2017 | ||||||||||||||
Standard | IEC 60137-2017 | |||||||||||||
Highest voltage for equipment Um | kV | 24 | 36 | 52 | 72.5 | 100 | 123 | 145 | 170 | 245 | 300 | 362 | ||
Rated frequency | Hz | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | ||
Dry power frequency withstand voltage 1minute |
kV | 50 | 70 | 95 | 140 | 185 | 230 | 275 | 325 | 460 | 460 | 510 | ||
Lightning impulse(BIL) | kV | 125 | 170 | 250 | 325 | 450 | 550 | 650 | 750 | 1050 | 1050 | 1175 | ||
Switching impulse(SIL) | kV | - | - | - | - | - | - | - | - | 850 | 850 | 950 | ||
Maximum Rated Current | A | 5000 | 5000 | 5000 | 4000 | 4000 | 4000 | 4000 | 3150 | 3150 | 3150 | 3150 | ||
Temperature range | ºC | Down to -60°C up to +55°C available on request | ||||||||||||
Key technical parameters-IEEE C57.19.01-2017 | ||||||||||||||
Standard | IEEE C57.19.01-2017 | |||||||||||||
Highest voltage for equipment Um | kV | 25 | 34.5 | 46 | 69 | 115 | 138 | 161 | 230 | 345 | ||||
Rated frequency | Hz | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | ||||
Dry power frequency withstand voltage 1minute |
kV | 60 | 80 | 105 | 160 | 260 | 310 | 365 | 425 | 520 | ||||
Lightning impulse(BIL) | kV | 150 | 200 | 250 | 350 | 550 | 650 | 750 | 900 | 1175 | ||||
Switching impulse(SIL) | kV | - | - | - | - | - | - | - | - | 825 | ||||
Maximum Rated Current | A | 5000 | 5000 | 5000 | 4000 | 4000 | 4000 | 3150 | 3150 | 3150 | ||||
Temperature range | ºC | Down to -60°C up to +55°C available on request |