Customization: | Available |
---|---|
Application: | High-voltage |
Material: | Composite Polymer |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
363kV RIP & RIS Bushings for Transformer
Rated Phase-to-Earth voltage: 210kV
Rated frequency: 50/60Hz
Rated current: 2500A
1 minute power frequency withstand voltage(dry): 560kV
Partial discharge level at 363kV: ≤5 pC
Tanδ of bushings (20ºC): ≤0.5%
Lightning impulse withstand voltage(dry): 1175kV
Switching impulse withstand voltage(dry): 950kV
Test tap voltage withstand level: 2kVrms
Rated thermal short-time current, 2sec: 62.5kA
Rated dynamic current (Id): 156.25kA
Installation angle: 0-90°
Minimum total creepage distance: 10600mm
Ambient temperature: -60°С +55°С
Cantilever test load: 5000N
Seismic stability on the MSK-64 scale: 9 points
Installation height above sea level: ≤1000m
Type of conductor: Bottom connection
Internal insulation: RIP
External insulation/Colour: Porcelain / Brown
Comply with standard: IEC 60137
Key technical parameters-IEC | ||||||||||||
Standard | IEC 60137-2017 | |||||||||||
Highest voltage for equipment Um | kV | 24 | 36 | 52 | 72.5 | 100 | 123 | 145 | 170 | 245 | 300 | 362 |
Rated frequency | Hz | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 |
Dry power frequency withstand voltage 1minute |
kV | 50 | 70 | 95 | 140 | 185 | 230 | 275 | 325 | 460 | 460 | 510 |
Lightning impulse(BIL) | kV | 125 | 170 | 250 | 325 | 450 | 550 | 650 | 750 | 1050 | 1050 | 1175 |
Switching impulse(SIL) | kV | - | - | - | - | - | - | - | - | 850 | 850 | 950 |
Maximum Rated Current | A | 5000 | 5000 | 5000 | 4000 | 4000 | 4000 | 4000 | 3150 | 3150 | 3150 | 3150 |
Temperature range | ºC | Down to -60°C up to +55°C available on request | ||||||||||
Key technical parameters-IEEE | ||||||||||||
Standard | IEEE C57.19.01-2017 | |||||||||||
Highest voltage for equipment Um | kV | 25 | 34.5 | 46 | 69 | 115 | 138 | 161 | 230 | 345 | ||
Rated frequency | Hz | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | ||
Dry power frequency withstand voltage 1minute |
kV | 60 | 80 | 105 | 160 | 260 | 310 | 365 | 425 | 520 | ||
Lightning impulse(BIL) | kV | 150 | 200 | 250 | 350 | 550 | 650 | 750 | 900 | 1175 | ||
Switching impulse(SIL) | kV | - | - | - | - | - | - | - | - | 825 | ||
Maximum Rated Current | A | 5000 | 5000 | 5000 | 4000 | 4000 | 4000 | 3150 | 3150 | 3150 | ||
Temperature range | ºC | Down to -60°C up to +55°C available on request |