Customization: | Available |
---|---|
Application: | High-voltage |
Material: | Porcelain |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Company: Shandong Chinsun Electrical Equipment Co., Ltd.
Key technical parameters-IEC 60137-2017 | ||||||||||||||
Standard | IEC 60137-2017 | |||||||||||||
Highest voltage for equipment Um | kV | 72.5 | 100 | 123 | 145 | 170 | 245 | 300 | 362 | 420 | 550 | |||
Rated frequency | Hz | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | |||
Dry power frequency withstand voltage 1minute |
kV | 140 | 185 | 230 | 275 | 325 | 460 | 460 | 520 | 650 | 710 | |||
Lightning impulse(BIL) | kV | 325 | 450 | 550 | 650 | 750 | 1050 | 1050 | 1175 | 1425 | 1550 | |||
Switching impulse(SIL) | kV | - | - | - | - | - | 850 | 850 | 950 | 1050 | 1175 | |||
Maximum Rated Current | A | 3150 | 3150 | 3150 | 3150 | 3150 | 3150 | 3150 | 3150 | 3150 | 3150 | |||
Temperature range | ºC | Down to -60°C up to +55°C available on request | ||||||||||||
Key technical parameters-IEEE C57.19.01-2017 | ||||||||||||||
Standard | IEEE C57.19.01-2017 | |||||||||||||
Highest voltage for equipment Um | kV | 69 | 115 | 138 | 161 | 230 | 345 | 500 | ||||||
Rated frequency | Hz | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 | ||||||
Dry power frequency withstand voltage 1minute |
kV | 160 | 185 | 310 | 365 | 425 | 520 | 750 | ||||||
Lightning impulse(BIL) | kV | 350 | 550 | 650 | 750 | 900 | 1175 | 1675 | ||||||
Switching impulse(SIL) | kV | - | - | - | - | - | 825 | 1175 | ||||||
Maximum Rated Current | A | 3150 | 3150 | 3150 | 3150 | 3150 | 3150 | 3150 | ||||||
Temperature range | ºC | Down to -60°C up to +55°C available on request |